Project overview

Fire pump room and hydrant network for a logistics center

Complete fire pump room, hydrant and monitor network, and acceptance testing for a 42,000 m² distribution center with high-bay racking.

Fire pump room and hydrant network for a logistics center

The challenge

A 42,000 m² distribution center with high-bay racks required a pumping system capable of simultaneously feeding the ESFR sprinkler network and the outdoor hydrant and monitor network, with the redundancy required by NFPA 20 and the insurer.

The public water supply could not guarantee the required pressure or flow, so the system had to be self-sufficient.

Technical scope

  • Pump room: two main pumps (electric and diesel) rated 2,500 GPM at 125 psi, jockey pump, listed controllers and automatic transfer switch.
  • Storage: two 1,200 m³ tanks with automatic fill and level monitoring.
  • Outdoor network: hydrant and monitor loop with supervised sectioning valves.
  • Integration: pump and valve status signals to the fire alarm panel and the building management system.
Fire pumps and valves

Execution

  1. Engineering: hydraulic calculation of the most demanding scenario (ESFR + hydrants), pump selection by certified curve and pump room design.
  2. Supply: direct import of UL/FM listed pumps, drivers, controllers and valves.
  3. Installation: mechanical, electrical, suction and discharge piping installation by specialized crews.
  4. Testing: field pump test per NFPA 20 (churn, 100% and 150% flow), hydrant flow test and delivery of the acceptance report.

Results

  • Field curves within tolerance of the factory-certified curves.
  • System approved by the insurer on the first inspection.
  • Preventive maintenance contract with weekly start-up tests and an annual performance test.
Inside the logistics center

“The pump is the heart of the system. If it does not start when needed, everything else is irrelevant.” — HWDE Engineering

More case studies

Explore more projects

All projects
Clean agent upgrade and maintenance of an existing system

Clean agent upgrade and maintenance of an existing system

Info:

Replacement of an obsolete suppression system with a clean agent system per NFPA 2001 in a data center, with room integrity testing and a predictive maintenance plan.

NFPA 2001 clean agent Room integrity test Predictive maintenance
Fire protection system for a manufacturing plant

Fire protection system for a manufacturing plant

Info:

Design, supply and installation of the sprinkler network, fire pump room and detection and alarm system of an 18,500 m² manufacturing plant, under NFPA 13, 20 and 72.

NFPA 13 sprinklers NFPA 20 fire pumps Detection and alarm

From risk analysis to the maintenance of your fire protection or hydrosanitary system, we are ready to support you. Write to us today and schedule a technical consultation with our engineers.

Let's protectyour operation